Rackmount On-Line UPS (Uninterruptable Power Supply) 3000VA (Model: OUP-3000-RM)

Rackmount On-Line UPS (Uninterruptable Power Supply) 3000VA (Model: OUP-3000-RM)

Rackmount On-Line UPS (Uninterruptable Power Supply) 3000VA (Model: OUP-3000-RM)

OUP-3000-RM
  • Overview
GENERAL INFORMATION
Power Rating 3KVA/2100W

AC INPUT
AC Input Voltage 100V:76V~130V 110V:80V~138V 115V:83.5V~140V 120V:87V~140V 208V:152V~260V 220V:160V~276V 230V:167V~280V 240V:174V~280V
AC Input Frequency 50 or 60 Hz+/-3 Hz
AC Input Phase Single
AC Input Power factor >= 0.98

AC OUTPUT
AC Output Voltage 100V/110V/115V/120V or 208V/220V/230V/240V
AC Output Frequency 50Hz/60Hz (Auto detection)
AC Output Frequency Stability (+/-0.5%)
AC Output Voltage Regulation (+/-2%)
AC Output Powerfactor 0.7 (lagging)
AC Output Hamonic distortion <3% of T.H.D. at linear load
AC Output Overload detection 105% for 10 seconds and 130% +/- 10% for 300ms

EFFICIENCY
Field49 > 85%

TRANSFER
Transfer Power failure Recovery 0 ms
Transfer Overload Disappear Auto transfer to UPS
Transfer UPS to By Pass or Vice Versa N/A

NOISE
Noise Level 1m Distance < 45dBA

PROTECTION
Protection Spike 150 Joules

BATTERY
Battery Type Sealed lead acid battery, free-maintenance
Battery Protection Cut off without draining any current when battery low
Battery DC Voltage 72V

BACKUP TIME
Battery Backup Time Full Load 9 minutes
Battery Backup Time Half Load 25 minutes
Battery Recharge Time About 8 hours to 90% after fully discharged

PHYSICAL
Physical Weight lbs Tower 81.4 lb
Physical Weight kgs RM 37
Physical Weight lbs RM N/A
Physical Dimension mm Tower 192x460x385
Physical Dimension inch Tower N/A
Physical Dimension mm RM N/A
Physical Dimension inch RM N/A

INDICATOR
LCD Indicators Status Line input (green), inverter output (green), bypass (yellow), fault (red)
LED LED

ALARM
Alarm Battery Discharge The first warning will beep every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition
Alarm UPS Fault Continuous beeping sound

INTERFACE
Interface Dry Contact Provide power management & diagnostic functions including power status, battery low, schedule UPS ON/OFF, battery/load level display and more. Compatatible with Windows 95/98/2000/ME/NT/XP, Novell Unix and other popular systems
Interface RS-232 Provide power management & diagnostic functions including power status, battery low, schedule UPS ON/OFF, battery/load level display and more. Compatatible with Windows 95/98/2000/ME/NT/XP, Novell Unix and other popular systems
Interface Option N/A

ENVIRONMENT
Environment Temperature 0 deg C ~ 40 deg C
Environment Humidity 0%~95% (Non condensing)
ShowOrder 79